Preaction/Deluge Valves 9- During the annual trip test, the 4.3.3.2 interior of the preaction or deluge valve shall be cleaned thoroughly and the parts replaced or repaired as necessary. Backflow Prevention Assemblies 9-6.2.1 All backflow preventers installed in fire protection system piping shall be tested annually Maintenance Control Valves 9-3.5 The operating stems of outside screw and yoke valves shall be lubricated annually. Dry Pipe Valves/Quick Opening Devices 9- Each dry pipe valve shall be 4.4.2.1 trip tested annually during warm weather.
WILCOM EMBROIDERY STUDIO E2 MINIMIZE CONNECTORS FULL
Preaction/Deluge Valves 9- Each deluge or preaction 4.3.2.2 valve shall be trip tested annually at full flow in warm weather and in accordance with the manufacturer’s instructions. Control Valves 9-3.4.1 Each control valve shall be operated annually through its full range and returned to its normal position. Waterflow Alarm 9-2.7 All waterflow alarms shall be tested quarterly in accordance with the manufacturer’s instructions.

Gauges 2-3.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. (See 'Valves' below) Antifreeze Solution 2-3.4 The freezing point of solutions in antifreeze shall be tested annually by measuring the specific gravity with a hydrometer or refractometer and adjusting the solutions if necessary. Spare Sprinkler Heads 2-2.1.3 The supply of spare sprinklers shall be inspected annually Valves (All Types) (See 'Valves' below) Testing Alarm Devices Main Drain 2-3.2 Waterflow alarm devices including, but not limited to, mechanical water motor gongs, vane-type waterflow devices, and pressure switches that provide audible or visual signals shall be tested quarterly. Sprinkler Heads 2-2.1.1 Sprinklers shall be inspected from the floor level annually. Pipe & Fittings 2-2.2 Sprinkler pipe and fittings shall be inspected annually from the floor level. Buildings 2-2.5 Annually, prior to the onset of freezing weather, buildings with wet pipe systems shall be inspected to verify that windows, skylights, doors, ventilators, other openings and closures, blind spaces, unused attics, stair towers, roof houses, and low spaces Hangers/Bracing 2-2.3 Sprinkler pipe hangers and seismic braces shall be inspected annually from the floor level.

Hydraulic Nameplate 2-2.7 The hydraulic nameplate, if of 8 Fire Sprinkler System provided, shall be inspected quarterly to verify that it is attached securely to the sprinkler riser and is legible.
WILCOM EMBROIDERY STUDIO E2 MINIMIZE CONNECTORS FREE
Control Valves (See 'Valves' below) Alarm Devices 2-2.6 Alarm devices shall be inspected quarterly to verify that they are free of physical damage. Gauges - Wet Pipe Systems 2-2.4.1 Gauges on wet pipe sprinkler systems shall be inspected monthly to ensure that they are in good condition and that normal water supply pressure is being maintained.
WILCOM EMBROIDERY STUDIO E2 MINIMIZE CONNECTORS CODE
Inspection and Testing Requirements for Fire Sprinkler Systems Sprinkler Systems Monthly Quarterly SemiAnnual Other annual Code NFPA 13 Inspection Gauges - Dry, PreAction & Deluge 2-2.4.2 Gauges on dry, preaction, and deluge systems shall be inspected weekly to ensure that normal air and water pressures are being maintained.

A trending comparison of year-by-year results can show early indication of problems before they are really serious.
WILCOM EMBROIDERY STUDIO E2 MINIMIZE CONNECTORS DRIVER
The report will include test results for operation of the pump, driver and controller. After the tests are completed, you will get a test report describing which tests were conducted and settings of all time delay devices. The activating elements have been removed so that when the control valve is opened water will flow from all of the sprinklers simultaneously and deluge the area with water.Īll functions of the fire pump controller should also be tested at least annually. Standard sprinklers are used, but they are all open. Deluge Sprinkler Systems of 8 Fire Sprinkler System The arrangement of deluge system piping is similar to a wet or dry pipe system with two major differences: A. Dry pipe sprinkler systems are installed in areas where wet pipe systems may be inappropriate such as areas where freezing temperatures might be expected. The release of this pressure (as from the opening of a sprinkler) permits the water pressure to open a valve known as a dry pipe valve and the water then flows into the piping system and out of the open sprinkler head. of 8 Fire Sprinkler System Dry Pipe Sprinkler Systems A dry pipe sprinkler system is a system with automatic sprinkler heads attached to a piping system containing air or nitrogen under pressure. Sprinklers for special applications are designed to discharge up to 100 gpm.